"V", "W", "X", "Y" and "Z" Transformer Desiccant BreathersTransformer Desiccant Breather sizes V, W and X breathers have a 3/4" female pipe thread; sizes Y and Z have a 1" female pipe thread.

Transformer Desiccant Breathers are also available as double and triple units.  Please contact us for details of the YY, ZZ and ZZZ assemblies.

 

SIZES V, W, X, Y, AND Z
DIMENSIONS
Size
Overall Length H
Diameter D
Female Pipe Thread Size
Charge Length J
Charge Diameter G
V
14.8" (375 mm)
10.0" (255 mm)
3/4"-14 BSPP but 3/4"-14 NPSM will work
8.94" (227 mm)
8.15" (207 mm)
W
21.9" (555 mm)
10.0" (255 mm)
3/4"-14 BSPP but 3/4"-14 NPSM will work
16.00" (407 mm)
8.15" (207 mm)
X
28.9" (735 mm)
10.0" (255 mm)
3/4"-14 BSPP but 3/4"-14 NPSM will work
23.10" (587 mm)
8.15" (207 mm)
Y
19.1" (485 mm)
14.0" (355 mm)

1" BSPP but
1"-11-1/2 NPSM will work

13.46" (342 mm)
12.05" (306 mm)
Z
25.4" (645 mm)
14.0" (355 mm)
1" BSPP but
1"-11-1/2 NPSM will work
19.76" (502 mm)
12.05" (306 mm)

SIZES V, W, X, Y, AND Z
Size
Desiccant Charge/ lb. (kg)
Maximum Recommended Reservoir Size Oil/ gal (liters)
V
11.02 lbs. (5.0 kg)
2,998 gal. (11,350 liters)
W
22.05 lbs. (10.0 kg)
5,997 gal. (22,700 liters)
X
31.97 lbs. (14.5 kg)
8,995 gal. (34,050 liters)
Y
38.58 lbs. (17.5 kg)
12,007 gal. (45,450 liters)
Z
60.19 lbs. (27.3 kg)
18,003 gal. (68,150 liters)

V, W, X, W, Z Transformer Breather

 